- Inlet
- Primary chamber
- Aeration chambers
- Diffusers
- Final (or ‘humus’) chamber
- Polylok filter
- Outlet
8. Recirculation to primary chamber
9. Turret guard
10. Carbon covers
11. High level alarm
12. Eco-friendly process contol
13. GRP kiosk
Benefits
Plant sizing
Bespoke design with optional tank sizes ranging from Ø1.9-3m satisfies the demands of site conditions. Each option is the same price.
Class-leading effluent quality
20:30:20mg/ltr (BOD:suspended solids:ammonia) effluent quality ensures discharge is well within national consent standards. Improved effluent quality to meet tighter consent standards can be achieved by Gaia design.
Heavy duty shell as standard
Structurally sound and built to last. Enables installation in all ground conditions.
High media surface area
High specification bio-media (310m3 per m2) and membrane diffusers provide even circulation to eliminate ‘dead spots’.
Eco-friendly process control
Energy-efficient, economical and flexible process control for minimal running, maintenance and servicing costs (see pages 24-25).
For sites that do not need the ability to regulate process control, Marsh can offer diaphragm compressors for sewage treatment plants up to 150PE
Internal recirculation
Continues the treatment process to provide higher effluent quality whilst balancing flow over 24 hour period or periods of intermittent use.
Polylok tertiary filter
All plants fitted with the patented Polylok tertiary filter to reduce suspended solids in the final effluent by a further 35%, whilst also reducing residual BOD and Ammonia levels.
Carbon covers (optional)
600mm carbon covers provide significant strength and durability, and helps to reduce possible odours.
Optional extras
Optional extras include extensions for deep installations, pumped outlets for sites with adverse levels, sample chambers, Degrilleur trash barriers, phosphate reduction and UV treatment chambers.
Specifications
Model up to | Width Ø +/- 50mm |
Length | Height | Inlet invert | Inlet Ø | Outlet invert | Outlet Ø | Turret Ø | Desludge (days) |
---|---|---|---|---|---|---|---|---|---|
55PE | 1900 | 6540 | 2500 | 750 | 160 | 900 | 160 | 600 | 90 |
60PE | 1900 | 7050 | 2500 | 750 | 160 | 900 | 160 | 600 | 90 |
75PE | 2500 | 5730 | 3100 | 900 | 160 | 1000 | 160 | 600 | 90 |
100PE | 2500 | 7080 | 3100 | 900 | 160 | 1000 | 160 | 600 | 90 |
125PE | 2500 | 7980 | 3100 | 900 | 160 | 1000 | 160 | 600 | 75 |
55PE | 1900 | 6540 | 2500 | 750 | 160 | 900 | 160 | 600 | 90 |
150PE | 2500 | 8640 | 3100 | 900 | 160 | 1000 | 160 | 600 | 60 |
175PE | 2500 | 9930 | 3100 | 900 | 160 | 1000 | 160 | 600 | 60 |
200PE | 2500 | 10200 | 3100 | 900 | 160 | 1000 | 160 | 600 | 45 |
225PE | 2500 | 11360 | 3100 | 900 | 160 | 1000 | 160 | 600 | 45 |
250PE | 2500 | 12530 | 3100 | 900 | 160 | 1000 | 160 | 600 | 45 |
275PE | 3000 | 9060 | 3800 | 1100 | 160 | 1300 | 160 | 750 | 30 |
300PE | 3000 | 9780 | 3800 | 1100 | 160 | 1300 | 160 | 750 | 30 |
350PE | 3000 | 11220 | 3800 | 1100 | 160 | 1300 | 160 | 750 | 30 |
400PE | 3000 | 12660 | 3800 | 1100 | 160 | 1300 | 160 | 750 | 30 |